260 Fault tracing
How to reset
The drive can be reset either by pressing the RESET key on the control panel or PC
tool, or by switching the supply voltage off for a while. When the fault has been
removed, the motor can be restarted.
A fault can also be reset from an external source selected by parameter
.
Fault history
When fault is detected, it is stored in the fault logger with a time stamp. The fault
history stores information on the 16 latest faults of the drive. Three of the latest faults
are stored at the beginning of a power switch off.
and
store the fault codes of the most
recent faults.
Alarms can be monitored via alarm words
Alarm information is lost at power switch off or fault reset.
Alarm messages generated by the drive
Code
Alarm
(fieldbus code)
Cause
What to do
2000
BRAKE START
TORQUE
(0x7185)
Programmable fault:
Mechanical brake alarm. Alarm
is activated if required motor
starting torque (
) is not achieved.
Check brake open torque setting,
parameter
Check drive torque and current limits.
See parameter group
.
2001
BRAKE NOT
CLOSED
(0x7186)
Programmable fault:
Mechanical brake control
alarm. Alarm is activated e.g. if
brake acknowledgement is not
as expected during brake
closing.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
To determine whether problem is with
acknowledgement signal or brake, check
if brake is closed or open.
2002
BRAKE NOT OPEN
(0x7187)
Programmable fault:
Mechanical brake control
alarm. Alarm is activated e.g. if
brake acknowledgement is not
as expected during brake
opening.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
To determine whether problem is with
acknowledgement signal or brake, check
if brake is closed or open.
2003
SAFE TORQUE OFF
(0xFF7A)
Programmable fault:
Safe Torque Off function is
active, i.e. safety circuit
signal(s) connected to
connector X6 is lost while drive
is stopped and parameter
is set to
.
Check safety circuit connections. For
more information, see appropriate drive
hardware manual.
2004
STO MODE CHANGE
(0xFF7A)
Error in changing Safe Torque
Off supervision, i.e. parameter
setting
could not be changed to value
.
Contact your local ABB representative.
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...