218 Parameters
56.03
Signal3 param
Selects the third signal to be displayed on the optional control
panel. The default signal is
.
00.00 … 255.255
3rd signal to be displayed.
-
56.04
Signal1 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
56.05
Signal2 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
56.06
Signal3 mode
Defines the way the signal selected by parameter
is displayed on the optional control panel.
Disabled
Signal not displayed. Any other signals that are not disabled
are shown together with their respective signal name.
-1
Normal
Shows the signal as a numerical value followed by unit.
0
Bar
Shows the signal as a horizontal bar.
1
Drive name
Shows the drive name. (The drive name can be set using the
DriveStudio PC tool.)
2
Drive type
Shows the drive type.
3
57
57 D2D
communication
Configuration of drive-to-drive communication. See also
section
on page
57.01
Link mode
Activates the drive-to-drive connection.
Disabled
Drive-to-drive connection disabled.
0
Follower
The drive is a follower on the drive-to-drive link.
1
Master
The drive is the master on the drive-to-drive link. Only one
drive can be the master at a time.
2
57.02
Comm loss func
Selects how the drive acts when an erroneous drive-to-drive
configuration or a communication break is detected.
No
Protection not active.
0
Alarm
The drive generates an alarm.
1
Fault
The drive trips on a fault.
2
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...