94 Parameters
Parameter listing
No.
Name/Value
Description
FbEq
01
01 Actual values
Basic signals for monitoring of the drive.
01.01
Motor speed rpm
Filtered actual speed in rpm. The used speed feedback is
defined by parameter
. The filter time
constant can be adjusted using parameter
100 = 1 rpm
01.02
Motor speed %
Actual speed in percent of the motor synchronous speed.
100 = 1%
01.03 Output frequency
Estimated drive output frequency in Hz.
100 = 1 Hz
01.04
Motor current
Measured motor current in A.
100 = 1 A
01.05
Motor current %
Motor current in percent of the nominal motor current.
10 = 1%
01.06
Motor torque
Motor torque in percent of the nominal motor torque. See also
parameter
10 = 1%
01.07
Dc-voltage
Measured intermediate circuit voltage.
100 = 1 V
01.08
Encoder1 speed
Encoder 1 speed in rpm.
100 = 1 rpm
01.09
Encoder1 pos
Actual position of encoder 1 within one revolution.
100000000 =
1 rev
01.10
Encoder2 speed
Encoder 2 speed in rpm.
100 = 1 rpm
01.11
Encoder2 pos
Actual position of encoder 2 within one revolution.
100000000 =
1 rev
01.12
Pos act
Actual position of encoder 1 in revolutions.
1000 = 1 rev
01.13
Pos 2nd enc
Scaled actual position of encoder 2 in revolutions.
1000 = 1 rev
01.14
Motor speed est
Estimated motor speed in rpm.
100 = 1 rpm
01.15
Temp inverter
Estimated temperature of drive heatsink in percent of fault
limit.
10 = 1%
01.16
Temp brk chopper
Brake chopper IGBT temperature in percent of fault limit.
10 = 1%
01.17
Motor temp1
Measured temperature of motor 1 in degrees Celsius.
10 = 1 °C
01.18
Motor temp2
Measured temperature of motor 2 in degrees Celsius.
10 = 1 °C
01.19
Used supply volt
Either the nominal supply voltage defined by parameter
, or, if auto-identification is enabled by
parameter
, the automatically
determined supply voltage.
10 = 1 V
01.20
Brake res load
Estimated temperature of the braking resistor. The value is
given in percent of the temperature the resistor reaches when
loaded with the power defined by parameter
1 = 1%
01.21
Cpu usage
Microprocessor load in percent.
1 = 1%
01.22
Power inu out
Drive output power in kW or hp, depending on setting of
parameter
.
100 = 1 kW
or hp
01.23
Motor power
Measured motor power in kW or hp, depending on setting of
parameter
.
100 = 1 kW
or hp
01.24
kWh inverter
Amount of energy that has passed through the drive (in either
direction) in kilowatt-hours.
1 = 1 kWh
01.25
kWh supply
Amount of energy that the drive has taken from the AC supply
in kilowatt-hours.
1 = 1 kWh
01.26
On-time counter
On-time counter. The counter runs when the drive is
powered. Can be reset using the DriveStudio PC tool.
1 = 1 h
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...