Program features 71
Settings
(page
).
The PID control macro can be activated from the control panel main menu by
selecting ASSISTANTS – Firmware assistants – Application Macro – PID control. See
also page
.
Programmable analog inputs
The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
t
<
t
d
t
d
SLEEP MODE
t
wd
t
wd
Motor Speed
t
d
= Sleep delay (
t
wd
= Wake-up delay (
Sleep level
(
)
STOP
START
Actual value
Actual value
Wake-up level
(
)
Time
Time
Time
Wake-up level
(
)
Non-inverted (source of
= 0)
Inverted (source of
= 1)