![ABB ACS850-04 series Firmware Manual Download Page 157](http://html1.mh-extra.com/html/abb/acs850-04-series/acs850-04-series_firmware-manual_3365228157.webp)
Parameters 157
22.06
Shape time acc1
Defines the shape of the acceleration ramp at the beginning
of the acceleration.
0.000 s: Linear ramp. Suitable for steady acceleration or
deceleration and for slow ramps.
0.001…1000.000 s: S-curve ramp. S-curve ramps are ideal
for lifting applications. The S-curve consists of symmetrical
curves at both ends of the ramp and a linear part in between.
Acceleration:
Deceleration:
0.000 … 1800.000
s
Ramp shape at start of acceleration.
1000 = 1 s
22.07
Shape time acc2
Defines the shape of the acceleration ramp at the end of the
acceleration. See parameter
0.000 … 1800.000
s
Ramp shape at end of acceleration.
1000 = 1 s
22.08
Shape time dec1
Defines the shape of the deceleration ramp at the beginning
of the deceleration. See parameter
0.000 … 1800.000
s
Ramp shape at start of deceleration.
1000 = 1 s
No.
Name/Value
Description
FbEq
> 0 s
= 0 s
Linear ramp:
Par.
= 0 s
S-curve ramp:
Par.
> 0 s
Speed
Time
S-curve ramp:
Par.
> 0 s
Linear ramp:
Par.
Linear ramp:
Par.
S-curve ramp:
Par.
Speed
Time
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...