![ABB ACS850-04 series Firmware Manual Download Page 276](http://html1.mh-extra.com/html/abb/acs850-04-series/acs850-04-series_firmware-manual_3365228276.webp)
276 Fault tracing
0309
APPL LOADING
(0x6300)
Corrupted application file
Note:
This fault cannot be
reset.
Reload application.
If fault is still active, contact your local
ABB representative.
0310
USERSET LOAD
(0xFF69)
Loading of user set is not
successfully completed
because:
- requested user set does not
exist
- user set is not compatible
with drive program
- drive has been switched off
during loading.
Reload.
0311
USERSET SAVE
(0xFF69)
User set is not saved because
of memory corruption.
Check the setting of parameter
If the fault still occurs, contact your local
ABB representative.
0312
UFF OVERSIZE
(0x6300)
UFF file is too big.
Contact your local ABB representative.
0313
UFF EOF
(0x6300)
UFF file structure failure
Delete faulty file or contact your local
ABB representative.
0314
TECH LIB
INTERFACE
(0x6100)
Incompatible firmware
interface
Note:
This fault cannot be
reset.
Contact your local ABB representative.
0315
RESTORE FILE
(0x630D)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
0316
DAPS MISMATCH
(0x5484)
Mismatch between JCU
Control Unit firmware and
power unit logic versions.
Contact your local ABB representative.
0317
SOLUTION FAULT
(0x6200)
Fault generated by function
block SOLUTION_FAULT in
the solution program.
Check the usage of the
SOLUTION_FAULT block in the solution
program.
0318
MENU HIDING
(0x6200)
Menu hiding file missing or
corrupted.
Reload application.
Contact your local ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...