238 Additional parameter data
Fieldbus addresses
Refer to the
User’s Manual
of the fieldbus adapter.
Pointer parameter format in fieldbus communication
Value and bit pointer parameters are transferred between the fieldbus adapter and
drive as 32-bit integer values.
32-bit integer value pointers
When a value pointer parameter is connected to the value of another parameter, the
format is as follows:
When a value pointer parameter is connected to a solution program, the format is as
follows:
Note:
Value pointer parameters connected to a solution program are read-only via
fieldbus.
Type
Data type. See enum, INT32, Bit pointer, Val pointer, Pb, REAL, REAL24,
UINT32.
UINT32
32-bit unsigned integer value.
Val pointer
Value pointer. Points to the value of another parameter.
Bit
30…31
16…29
8…15
0…7
Name
Source type
Group
Index
Value
1
-
1…255
1…255
Description
Value pointer is
connected to
parameter
-
Group of source
parameter
Index of source
parameter
Bit
30…31
24…29
0…23
Name
Source type
Not in use
Address
Value
2
-
0…2
23
Description
Value pointer is
connected to solution
program.
-
Relative address of
solution program
variable
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...