98 Parameters
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
Log.
Par.
(continued)
9
Jogging 1
1
Activate Jogging 1. See section
.
OR
0
Jogging 1 disabled.
10
Jogging 2
1
Activate Jogging 2. See section
.
OR
0
Jogging 2 disabled.
11
Remote
cmd
1
Fieldbus control enabled.
–
–
0
Fieldbus control disabled.
12
Ramp out 0
1
Force output of Ramp Function Generator to zero. The
drive ramps to a stop (current and DC voltage limits
are in force).
–
–
0
No action.
13
Ramp hold
1
Halt ramping (Ramp Function Generator output held).
–
–
0
No action.
14
Ramp in 0
1
Force input of Ramp Function Generator to zero.
–
–
0
No action.
15
Ext1 / Ext2
1
Switch to external control location EXT2.
OR
0
Switch to external control location EXT1.
16
Req startinh
1
Activate start inhibit.
–
–
0
No start inhibit.
17
Local ctl
1
Request local control for Control Word. Used when the
drive is controlled from a PC tool or panel or local
fieldbus.
• Local fieldbus: Transfer to fieldbus local control
(control through fieldbus Control Word or
reference). Fieldbus steals the control.
• Panel or PC tool: Transfer to local control.
–
–
0
Request external control.
18
FbLocal ref
1
Request fieldbus local control.
–
–
0
No fieldbus local control.
19…27 Reserved
28
CW B28
Freely programmable control bits. See parameters
and the user manual of the fieldbus adapter.
–
–
29
CW B29
30
CW B30
31
CW B31
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...