178 Parameters
PTC 2nd FEN
The temperature is supervised using a PTC sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
6
Pt100 JCU x1
The temperature is supervised using a Pt100 sensor
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
7
Pt100 JCU x2
The temperature is supervised using two Pt100 sensors
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
8
Pt100 JCU x3
The temperature is supervised using three Pt100 sensors
connected to analog input AI1 and analog output AI1 on the
JCU Control Unit of the drive.
9
Pt100 Ext x1
The temperature is supervised using a Pt100 sensor
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
10
Pt100 Ext x2
The temperature is supervised using two Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
11
Pt100 Ext x3
The temperature is supervised using three Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
12
31.03
Mot temp1 almLim
Defines the alarm limit for motor thermal protection 1 (when
parameter
0 … 200 °C
Motor overtemperature alarm limit.
1 = 1 °C
31.04
Mot temp1 fltLim
Defines the fault limit for the motor thermal protection 1 (when
parameter
0 … 200 °C
Motor overtemperature fault limit.
1 = 1 °C
31.05
Mot temp2 prot
Selects how the drive reacts when motor overtemperature is
detected by motor temperature protection 2.
No
Motor temperature protection 2 inactive.
0
Alarm
The drive generates alarm MOTTEMPAL2 when the
temperature exceeds the alarm level defined by parameter
1
Fault
The drive generates alarm MOTTEMPAL2 or trips on fault
MOTTEMP2 when the temperature exceeds the alarm/fault
level defined by parameter
/
(whichever is lower).
2
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...