176 Parameters
30.07
Sto diagnostic
Selects how the drive reacts when the drive detects that the
Safe Torque Off function is active while the drive is stopped.
The Safe Torque Off function disables the control voltage of
the power semiconductors of the drive output stage, thus
preventing the inverter from generating the voltage required
to rotate the motor. For the wiring of the Safe Torque Off
circuit, see the appropriate hardware manual.
Notes:
• This parameter is for supervision only. The Safe Torque Off
function can activate even when this parameter is set to
• Fault STO 1 LOST / STO 2 LOST is activated if safety
circuit signal 1/2 is lost when the drive is in stopped state
and this parameter is set to
Fault
The drive trips on fault SAFE TORQUE OFF.
1
Alarm
The drive generates alarm SAFE TORQUE OFF.
2
No
No action taken.
3
30.08
Cross connection
Selects how the drive reacts to incorrect input power and
motor cable connection (i.e. input power cable is connected
to drive motor connection).
No
No action taken.
0
Fault
The drive trips on fault CABLE CROSS CON.
1
30.09
Stall function
Selects how the drive reacts to a motor stall condition. The
protection wakes up if
• the drive is at stall current limit (defined by parameter
or
differs from 0
• the output frequency is below the level set by parameter
, and
• the conditions above have been valid longer than the time
set by parameter
See section
Stall protection (parameters 30.09…30.12)
page
.
30.10
Stall curr lim
Stall current limit in percent of the nominal current of the
motor. See parameter
0.0 … 1600.0%
Stall current limit.
10 = 1%
30.11
Stall freq hi
Stall frequency limit. See parameter
.
0.5 … 1000.0 Hz
Stall frequency limit.
10 = 1 Hz
30.12
Stall time
Stall time. See parameter
0 … 3600 s
Stall time.
1 = 1 s
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm upon a stall condition.
2
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault upon a stall condition.
Summary of Contents for ACS850-04 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 4: ......
Page 10: ...10 Table of contents...
Page 52: ...52 The ACS850 control panel...
Page 56: ...56 Control locations and operating modes...
Page 80: ...80 Program features...
Page 236: ...236 Parameters...
Page 286: ...286 Fieldbus control...
Page 294: ...294 Control block diagrams...