ACS2000 User manual
2UEA001270 Rev. F
6-15 (16)
Chapter 6 - Electrical installation
6.7.2
Cable preparation
The control cables are entered either through the top or the bottom of the
terminal entry unit.
Punch the aluminum plate being used for cable entry as required for the
cables.
6.7.2.1 Cable routing
Route the cables through the steel access plate to termination on the right
side wall in the control compartment where the IOEC I/O control
connections and the fieldbus interface devices are rail mounted.
See Chapter 2 - Power electronics and cabinet features, 2.4.1 Auxiliary
power supply for auxiliary current and power specifications.
Figure 6-12 Auxiliary, control, and fieldbus cable entry
6.7.2.2 Determining the cable length
Determine the required length of a cable between the point of entry and
the connection point inside the cabinet and cut the cable to the required
length before connection to avoid excess cable in the raceway.
Legend
1
Top access panel
2
Top cable route
3
Customer
raceway
4
Bottom cable
route
5
Bottom access
panel
6
PE terminals
7
Standard IOEC2
customer
communication
module
8
Optional IOEC4
customer
communication
module
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......