6-12 (16)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 6 - Electrical installation
NOTICE
High voltages will be present in the terminal entry unit. High voltages can
cause flashover between the potential of different phase conductors and
the potential of a phase conductor and earth.
Therefore, a minimum clearance of 55 mm [2 in] must be maintained
between each cable and the terminals of any other phase, and a minimum
of 75 mm [3 in] from each cable to any exterior cabinet wall.
Busbar details
•
Busbar thickness: 6.4 mm [0.25 in]
•
Hole diameter for fastening bolts: 13 mm [0.5 in]
•
The busbars are suitable for both IEC and NEMA lug-type cable
connectors.
6.6.3.3 Bolted busbar connections
Material requirements
Use galvanized bolts and nuts as specified in Table 6-2.
Table 6-2
Hardware requirements
Connection type
This connection (see Figure 6-9) is recommended when connecting a
cable lug (3) to a busbar (4):
Figure 6-9
Connection with Belleville spring and flat washer
Bolt size
Grade
Dry torque value
M12
8.8
54 Nm
1/2 inch
5
40 ft-lbs
Legend
1
Belleville washer
2
Flat washer
3
Cable lug
4
Busbar
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......