ACS2000 User manual
2UEA001270 Rev. F
8-13 (18)
Chapter 8 - Local operation
8.7.1
Procedure for disconnecting the drive from the main power supply
1
Stop the motor as
described in the
previous section.
When the motor has reached zero speed, the display shows
ReadyRun.
2
Press the SUPPLY
OFF pushbutton to
disconnect the drive
from the main power
supply.
The following takes place:
•
The MV switchgear opens.
•
The DC link discharges.
While the DC link discharges, the display shows
OffSeqOn.
•
The SUPPLY OFF pushbutton flashes and changes to a
steady light when the DC link is discharged completely.
When the DC link is discharged, the display shows
ReadyOn.
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
OffSeqOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......