ACS2000 User manual
2UEA001270 Rev. F
5-11 (14)
Chapter 5 - Mechanical installation
5.4.5.1 Redundant fan installation procedure - Frames 2, 3
Consider the size and weight of the components when planning to lift them
onto the top of drive.
The fan components can be lifted by means of a forklift or a crane.
1
Remove the cover and the fan from the redundant fan assembly.
.
Figure 5-6 - Frames 2, 3
Redundant fan box
2
Remove the fan hole cover plate from the top of the drive.
3
Lift and properly orientate the empty redundant fan box on top of the
drive, being careful not to damage the sealing gasket.