ACS2000 User manual
2UEA001270 Rev. F
9-21 (24)
Chapter 9 - CDP control panel
9.4.1.4 Locking local or remote control mode
Accidental switching from remote control to local control can be prevented
with the lock function of parameter 16.04.
The parameter 16.04 LOCAL LOCK locks or unlocks the LOC / REM key
of the CDP control panel and determines the control place where the lock
function is activated (CDP control panel or remote control location).
Enable lock function
The lock function is disabled if the parameter 16.04 is set to 1 (= OPEN).
Switching from local to remote and vice versa is possible.
Disable lock function
The lock function is enabled if the parameter 16.04 is set to 2 (= LOCKED).
In this case, local cannot be selected on the CDP control panel. However,
the CDP control panel or the DriveWindow PC will remain in local mode (if
they were already in local mode when the parameter was set to locked)
until the CDP control panel is switched to remote.
The letter L remains on the display until the LOC / REM key is pressed.
2
To select remote
control, press the
LOC / REM key. The
remote control
location is indicated by
a blank (see arrow).
3
The keypad can also
be used as a remote
control place. In this
case, the parameters
11.01, 11.02, 12.03 or
12.06 must be set to
KEYPAD. In this setup
the remote control
location is indicated by
the letter R. The
START/STOP
commands and the
reference value can
be set from the CDP
control panel.
1
600.0 rpm
StateINU
MOTOR SP
POWER
ReadyRun
0.00 rpm
0.0 kW
0
Remote control location
1 R
600.0 rpm
StateINU
MOTOR SP
POWER
ReadyRun
0.00 rpm
0.0 kW
0
Remote control location
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......