ACS2000 User manual
2UEA001270 Rev. F
5-9 (14)
Chapter 5 - Mechanical installation
Figure 5-8 - Frame 1 Redundant fan power supply connections
6
Bolt the fan inlet ring to the top of the drive.
Figure 5-9 - Frame 1 Inlet ring installation
7
Install the fan in the fan box.
Figure 5-10 - Frame 1
Fan installation
8
Route the fan wires (see Figure 5-10 - Frame 1) and connect to the
terminal block.
9
Check that the flapper is moving freely.
10
Reattach the front panel and the cover of the fan unit.
100(U1)
W12210
W1221
1
W12212
107(TK2)
101(V1)
102(W1)
PE
W122PE2
103(U2)
104(V2)
105(W2)
106(TK1)
Legend
1
Terminal block X22
2
Wire numbers
3
Redundant fan
power supply
Legend
1
Fan inlet ring
Legend
1
Fan
2
Fan wires
3
Terminal block
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......