3-16 (26)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 3 - Control system
3.3.2.1 IOEC2 (A1541) digital outputs
Table 3-4
Standard digital output signal allocation
Terminal Channel
Default setting
Par. Group
X21-1
DO01
Ready on
(drive is ready for operation)
X21-2
X21-3
X22-1
DO02
Ready ref
(drive is running)
X22-2
X22-3
X23-1
DO03
Alarm/fault
(alarm is pending)
X23-2
X23-3
X24-1
DO04
Tripped
(drive has shut down)
X10 Terminal
Block *
X24-2
X24-3
X25-1 *
DO05
MV switchgear open command
(low active)
X25-2 *
X25-3 *
X26-1 *
DO06
MV switchgear closed command
(high active)
X26-2 *
X26-3 *
* Factory installed wiring for X10 terminal block. See Appendix G - MV
switchgear guide, located on the CD, for additional MV switchgear
control information.
When the integral input contactor disconnect is installed, X10 is
internal to the drive. Refer to Appendix P.
DC voltage Current
Switching
Continuous
24 VDC
8A
6A
48 VDC
1A
6A
120 VDC
0.4A
6A
AC voltage Current
Switching
Continuous
24 VAC
8A
6A
48 VAC
8A
6A
120 VAC
8A
6A
230 VAC
8A
6A
NC
NO
NC
NO
NC
NO
NC
NO
105T
104B
105B
106B
106T
107T
NC
NO
NC
NO
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......