8-14 (18)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 8 - Local operation
3
Turn the grounding
switch to the
grounded position
when the GROUND
SW RELEASED pilot
light is on.
NOTICE
The auxiliary voltage must be applied, switched on, to operate the
grounding switch.
Do not turn the grounding switch to the grounded position before the
light GROUND SW RELEASED is on. Otherwise, the switch will be
damaged.
The pilot light illuminates only after the fan stops. The fan runs
continuously for a preset time after the main power supply has been
switched off to dissipate the heat from the drive.
If the pilot light does not illuminate and there is reason to believe that
the grounding circuit is malfunctioning, see Chapter 10 -
Troubleshooting and maintenance, 10.3.4 Malfunctioning grounding
switch for further information.
When the grounding switch is in the grounded position, the status
line of the display alternates between DCGnd NOpen,
NotReadyOn, AFE NotRdy.
1 L ->
600.0 rpm
StateINU
DCGnd NOpen
MOTOR SP
0.00 rpm
POWER
0.0 kW
DCGnd NOpen
NotReadyOn
AFE NotRdy
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......