5-12 (14)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 5 - Mechanical installation
.
Figure 5-7 - Frames 2, 3
Redundant fan installation
4
Fasten the fan unit using the supplied screws. The predrilled holes
(see Figure 5-4 - Frames 2, 3) are fitted with press nuts on the
underside.
5
Make the terminal block to drive wiring connections.
The rear panel of the fan box may be removed for easier access to
the wiring.
A
Remove the upper IFU (Input Filter Unit) panel to access the
drive wiring for the redundant fan.
B
Carefully feed the wires from the drive up into the fan unit
housing and route to the terminal block.
C
Make the wiring connections.
Figure 5-8 - Frame 2
Redundant fan power supply connections
W12304
W12305
W12306
W123PE1
100(U1)
107(TK2)
101(V1)
102(W1)
PE
103(U2)
104(V2)
105(W2)
106(TK1)
Legend
1
Terminal block X23
2
Wire numbers
3
Redundant fan
power supply
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......