ACS2000 User manual
2UEA001270 Rev. F
3-5 (26)
Chapter 3 - Control system
3.2.1.1 Communication with IOEC I/O system
The AMC circuit board of the INU and the IOEC I/O system communicate
via two DDCS fiber-optic communication links, DDCS TX (for sending data),
DDCS RX (for reading data), and an optional MCB-OFF optical input. The
fiber-optic cables are connected to channel 7 of the AMC circuit boards.
3.2.1.2 Control tasks
Each AMC circuit board has specific control and closed-loop tasks
assigned to it.
•
The AMC circuit board of the AFE handles all rectifier and line-related
functions of the drive.
•
The AMC circuit board of the INU handles all other control tasks. It
processes drive and status information, performs the speed and
torque control tasks, and monitors the operation of the drive.
It continuously monitors all relevant drive variables (e.g. speed,
current, voltage). Pre-programmed internal protection functions
ensure that these variables remain within safe operating limits.
Optionally, the drive offers monitoring of signals from external
equipment. These can be activated and adjusted by parameter
settings.
Other general control, protection and monitoring tasks are
implemented within the drive, including control and monitoring of the:
•
MV switchgear
•
grounding switch
•
cooling system
See Appendix M - Signal and parameter table, located on the CD, for
further information on control, protection and monitoring functions.
3.2.1.3 MV (Medium Voltage) switchgear
The MV switchgear is a major switching and protection device for the drive
system.
This switchgear connects/disconnects the main power supply to the drive
and is required to operate upon the drive’s commands. The drive must
have exclusive control over the switchgear as part of the pre-charge
sequence of operation and discharging of the DC link.
NOTICE
The ACS2000 must have exclusive control of closing the MV switchgear.
Uncontrolled closing of the switchgear may cause damage to the drive.
See Appendix G - MV switchgear guide for control details. ACS2000
supplied with the optional integral input contactor disconnect has this
switching integral to the drive. See Appendix P for details.
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......