ACS2000 User manual
2UEA001270 Rev. F
9-23 (24)
Chapter 9 - CDP control panel
9.4.3
Entering a setpoint
A setpoint can be changed at any time if the CDP control panel has been
set to local.
1
To enter a control
panel mode displaying
the status row, press a
mode key.
2
To enter the setpoint
setting function, press
the REF key.
3
To change the
setpoint, press either
the corresponding fast
or slow navigation
key.
4
To exit the setpoint
setting mode, press
any of the mode keys.
1 L ->
600.0 rpm
StateINU
MOTOR SP
POWER
ReadyRun
600.00 rpm
75.0 kW
0
1 L ->
[600.0 rpm]
StateINU
MOTOR SP
POWER
ReadyRun
600.00 rpm
75.0 kW
0
1 L ->
[550.0 rpm]
StateINU
MOTOR SP
POWER
ReadyRun
600.00 rpm
75.0 kW
0
1 L ->
550.0 rpm
StateINU
MOTOR SP
POWER
ReadyRun
550.00 rpm
75.0 kW
0
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......