8-4 (18)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 8 - Local operation
the reference value is set at the higher-level control system. When in local
control mode, the value is entered into the CDP control panel.
Stopping indicates that the drive has received a stop command and that
a stop ramp, stop torque or coast stop has been initiated. The stopping
mode depends on the setting of parameter 21.02, STOP FUNCTION. The
status indication changes to ReadyRun when the zero speed threshold is
reached.
When a start command is given while the drive is stopping, the drive
resumes operation and the status indication changes to ReadyRef again.
This status message indicates that a fault condition has occurred that
requires a shutdown of the drive. The status message always alternates
with the specific fault message. The type of shutdown depends on the fault
class that the fault condition is assigned to in the drive software.
Stopping
Tripped
Summary of Contents for ACS2000 DFE
Page 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Page 2: ......
Page 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Page 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Page 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Page 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Page 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Page 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Page 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Page 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Page 213: ......