11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
155/174
Example:
In the above example:
+Fault MCB Disturb
is the reason for the failure of the drive, as it occurred first.
3.
+Warn Undervoltage
occurred approx. 3 sec after the first fault.
+Fault Undervoltage
immediately followed the warning.
-Fault RESET FAULT
informs that the fault has been reset.
11.3.4
Standard troubleshooting procedure
If a fault shuts down the drive, proceed as follows:
1. -Fault RESET FAULT
2011-04-26 14:57:56.5370
2. +Fault Undervoltage
2011-04-26 14:47:41.1110
3. +Warn Undervoltage
2011-04-26 14:47:41.1000
4. +Fault MCB Disturb
2011-04-26 14:47:38.0230
For more information on alarms and faults, see
“Appendix G - Signal and parameter table”.
1. Do not switch off the auxiliary supply voltage or try to reset a fault message
before all information at the time of the occurrence of the fault condition has
been saved.
2. Select the fault history display on the CDP control panel, but do not clear the
buffer!
For more information, see “10 CDP control panel” on page 125.
3. Identify the fault and make a logbook entry.
4. Save the content of the data logger when a PC is available that has the
DriveWindow or DriveDebug tool installed.
The data logger provides information (eg, waveforms of voltage, current,
torque) for efficient troubleshooting.
5. Contact ABB service if a fault cannot be rectified.
When calling ABB service, it is recommended to have the following data available
at the time when the fault occurred:
- Operating, ambient and load conditions
- Unusual events
6. After the fault has been rectified, start the drive as described in “09
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......