11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
170/174
11.6.10.2 Replacing a battery
CAUTION
⚠
1. When the drive is in operation, disable the battery monitoring function first. To do this, set
parameter
31.05 DISABLE BATTERY TEST
to ON.
Note:
Parameter 31.05 is automatically set to OFF after 1 hour.
2. Disconnect the wires (1 in Fig. 11-7).
3. Unscrew the battery (2 in Fig. 11-7).
4. Remove the cable duct covers (3 in Fig. 11-7)
Figure 11-7: Control compartment - replacing the batteries
5. Install the new battery in reverse order of removal.
6. Record the date of battery replacement in the logbook
~10 kg
Each battery weighs approximately 10 kg!
1
3
3
3
2
2
8 mm