07 ELECTRICAL INSTALLATION
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
7.5
Power cables, ground cables and equipotential
bonding conductor
7.5.1
Safety
▲
WARNING
⚠
NOTICE
7.5.2
Determining the cable length
1. Determine the required length of a cable between the point of entry and the connection
point inside the cabinet.
2. Cut the cable to the required length before connection.
See layout drawing in “Appendix C – Mechanical drawings” for information on:
- Project-specific cable entry
- Distance between point of cable entry and terminals
- Busbar and fastening hole dimensions
- Busbar designations
See “Appendix D – Wiring diagrams” for information on:
- Conventions for cross-reference and device identification
Risk of flashover!
- If the drive is supplied with an input voltage higher than 6.9 kV, there is a risk
of flashover between a conductor and the cabinet.
- To prevent flashover, install the insulating barrier as described.
Risk of damage or malfunction!
- Waste inside the cabinet can cause damage or malfunction.
- If possible, do not cut cables inside the terminal compartment. Retrieve any
waste which accidentally dropped into the cabinet.
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......