11 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
171/174
11.6.11 Replacing a fan unit
CAUTION
⚠
1. Disconnect all power supplies to the drive and ground the drive.
2. To isolate the fan from the auxiliary power supply, switch off the motor starter of the fan.
3. Unplug the power supply cable of the fan.
4. Unplug the supply cable of the fan inside of the drive.
5. Remove the cover.
6. Remove the fastening screws of the top plate.
7. Attach lifting gear appropriate for the weight of the impeller and the motor and then lift off
the top plate with the impeller attached to it.
~100 kg
Heavy load!
The fan weighs approximately 50 kg.
For more information, see “11.6.2 De-energizing the drive locally” on page 160.
13 mm
13 mm