03 POWER ELECTRONICS AND CABINET FEATURES
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
47/174
3.4.11.4
Starting, stopping the cooling system
The drive switches on the cooling system when the main circuit breaker (MCB) closes. When the
MCB opens, the cooling system switches off after a delay. The delay corresponds to the
discharging time of the drive and takes up to 5 minutes.
3.4.11.5
AC redundant fans - operating principles
Default settings:
- Cycle time during which AC fan 1 and AC fan 2 run alternately: 10 h
- Operating time of AC fan 1: 6 h
- Operating time of AC fan 2: 4 h
Figure 3-17: Operating times of the AC fan units during continuous drive operation (
A
) and
Intermittent drive operation (
B
)
(1) Cycle time
(2) Group 1
(3) Group 2
(4) 10 hours: default cycle time during which fan 1
and fan 2 run alternately
(5) 6 hours: default operating time of fan 1 (group 1)
(6) 4 hours: default operating time of fan 2 (group 2)
(7) On
(8) Off
1
2
3
4
4
5
5
6
A
B
7
8
7
8
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......