09 OPERATION
3BHS206977 E01 REV H
ACS1000I AIR-COOLED
USER MANUAL
120/174
- If a fault cannot be reset, it must be rectified by the responsible personnel.
- When no alarms and faults are present and the drive is ready, the CDP control panel
displays
RdyForMCBOn
:
3. Press the
MAIN SUPPLY ON
pushbutton on the control compartment door to close the MCB
and charge the DC link.
- The pushbutton lights up.
- The status line of the CDP control panel changes to
Charging
.
After charging has been finished, the following takes place:
- The protection IGCTs are closed.
- The status line of the CDP control panel changes to
Rdy to Strt
and the motor can
be started.
4. Enter the reference value.
LOC
RESET
REF
REM
1 L ->
0.0 rpm
Status
RdyForMCBon
MotorSpeed 0.00 rpm
Power
0.0 %
1 L ->
0.0 rpm
Status
Charging
MotorSpeed 0.00 rpm
Power
0.0 %
1 L ->
0.0 rpm 0
Status
Ready to Strt
MotorSpeed 0.00 rpm
Power
0.0 %
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......