7.5.5.3
Bolted connections
7.5.5.3.1
Material requirements
Use stainless steel bolts and nuts with the appropriate steel grade and property class for the
connection (recommended: A2-70 [designation according to ISO 3506]).
Note:
Nuts with bonded coating can be used as an alternative to uncoated stainless steel nuts.
7.5.5.3.2
Connection type
The following connection type is recommended when a cable lug (4 in Fig. 7-10) is connected
to a busbar:
- Spring washer (1 in Fig. 7-10) and flat washer (2 in Fig. 7-10) on each side of the busbar
(3 in Fig. 7-10).
Note:
Other washers can be used, provided they maintain the required contact pressure.
Figure 7-10: Bolted busbar connections
- Use cable lugs suitable for M12 bolts.
- If two conductors are used per phase, install the second conductor on the opposite side of
the busbar.
7.5.5.3.3
Lubrication
- If stainless steel bolts and nuts are used, lubricate the thread and head contact surface of
the bolt using recommended pasts, eg, Molykote D paste.
Note:
If a coated nut (eg, with bonded molybdenum-disulfide [MoS
2
] coating) is used, the
connection does not have to be lubricated.
7.5.5.4
Tightening torque
- Tighten bolted connections with bolts of sizes M10 and greater with the recommended
nominal torque for the bolt size used.
(1) Spring washer
(2) Flat washer
(3) Busbar
(4) Cable lug
1
2
3
4
2
1
Summary of Contents for ACS1000i air-cooled
Page 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000i air cooled User manual ...
Page 3: ...Contents ACS1000i air cooled User manual ...
Page 5: ... 01 About this manual 01 5 16 ...
Page 16: ......
Page 17: ... 02 Important safety information 02 17 28 ...
Page 28: ......
Page 29: ... 03 Power electronics and cabinet features03 29 56 ...
Page 57: ... 04 Control system 04 57 70 ...
Page 71: ... 05 Transportation storage and disposal05 71 78 ...
Page 78: ......
Page 79: ... 06 Mechanical installation 06 79 88 ...
Page 88: ......
Page 89: ... 07 Electrical installation07 89 104 ...
Page 105: ... 08 Commissioning 08 105 110 ...
Page 110: ......
Page 111: ... 09 Operation 09 111 124 ...
Page 125: ... 10 CDP control panel 10 125 148 ...
Page 149: ... 11 Preventive and corrective maintenance 11 149 172 ...
Page 173: ......