9.3.8
Technical data
Table 171:
ROV2PTOV (59N) technical data
Function
Range or value
Accuracy
Operate voltage, step 1
(1-200)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Operate voltage, step 2
(1–100)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Reset ratio
> 98%
-
Inverse time
characteristics for low and
-
See table
Definite time setting, step
1
(0.00–6000.00) s
± 0.5% ± 25 ms
Definite time setting, step
2
(0.000–60.000) s
± 0.5% ± 25 ms
Minimum operate time for
step 1 inverse
characteristic
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time, pickup
function
30 ms typically at 0 to 2 x V
set
-
Reset time, pickup
function
40 ms typically at 2 to 0 x V
set
-
Critical impulse time
10 ms typically at 0 to 1.2 xV
set
-
Impulse margin time
15 ms typically
-
9.4
Overexcitation protection OEXPVPH (24)
9.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Overexcitation protection
OEXPVPH
U/f >
SYMBOL-Q V1 EN
24
9.4.2
Functionality
When the laminated core of a power transformer or generator is subjected to a magnetic
flux density beyond its design limits, stray flux will flow into non-laminated components
1MRK 502 048-UUS A
Section 9
Voltage protection
299
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...