7.3
Loss of excitation LEXPDIS (40)
7.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of excitation
LEXPDIS
<
SYMBOL-MM V1 EN
40
7.3.2
Functionality
There are limits for the low excitation of a synchronous machine. A reduction of the
excitation current weakens the coupling between the rotor and the stator. The machine
may lose the synchronism and start to operate like an induction machine. Then, the
reactive power consumption will increase. Even if the machine does not loose
synchronism it may not be acceptable to operate in this state for a long time. Reduction of
excitation increases the generation of heat in the end region of the synchronous machine.
The local heating may damage the insulation of the stator winding and the iron core.
To prevent damages to the generator it should be tripped when excitation becomes too
low.
The impedance measurement is used for LEXPDIS function. Its operating characteristic
is designed as two zone, offset mho circles and a directional element restrain line.
7.3.3
Function block
ANSI0700031-1-en.vsd
LEXPDIS (40)
I3P*
V3P*
BLOCK
BLKTRZ1
BLKTRZ2
TRIP
TRZ1
TRZ2
PICKUP
PU_Z1
PU_Z2
XOHM
XPERCENT
ROHM
RPERCENT
ANSI0700031 V1 EN
Figure 70:
LEXPDIS (40) function block
1MRK 502 048-UUS A
Section 7
Impedance protection
167
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...