be reset by setting the
Clear accum. breaking curr
setting to on in the clear menu from
LHMI.
Alarm limit check
The
IACCALM
alarm is activated when the accumulated energy exceeds the value set with
the
AccCurrAlmLvl
threshold setting. However, when the energy exceeds the limit value
set with the
AccCurrLO
threshold setting, the
IACCLOAL
output is activated.
The
IACCALM
and
IACCLOAL
outputs can be blocked by activating the binary input
BLOCK
.
14.17.7.6
Remaining life of the circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wear off. The
breaker wear off depends on the tripping current. The remaining life of the breaker is
estimated from the circuit breaker trip curve provided by the manufacturer. The remaining
life is decremented at least by one when the circuit breaker is opened. The operation of the
remaining life of the circuit breaker subfunction can be described by using a module
diagram. All the modules in the diagram are explained in the next sections.
CB life
estimator
POSCLOSE
CBCNTRST
BLOCK
Alarm limit
check
CBLIFEAL
BLK_ALM
I3P
I_A
I_B
I_C
GUID-1565CD41-3ABF-4DE7-AF68-51623380DF29-ANSI V1 EN
Figure 272:
Functional module diagram for estimating the life of the circuit breaker
Circuit breaker life estimator
The circuit breaker life estimator module calculates the remaining life of the circuit
breaker. If the tripping current is less than the rated operating current set with the
RatedOpCurr
setting, the remaining operation of the breaker reduces by one operation. If
the tripping current is more than the rated fault current set with the
RatedFaultCurr
setting, then remaining operations of the circuit breaker are reduced by the
OperNoRated/
OperNoFault
value. The remaining life due to the tripping current in between these two
values is calculated based on the trip curve given by the manufacturer. The
OpNumRatCurr
and
OPNumFaultCurr
parameters set the number of operations the
breaker can perform at the rated current and at the rated fault current, respectively.
1MRK 502 048-UUS A
Section 14
Monitoring
613
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...