I1RANG
INTEGER
I1Amplitude range
I1ANGL
REAL
I1 Angle
I2
REAL
I2 Amplitude
I2RANG
INTEGER
I2 Magnitude range
I2ANGL
REAL
I2Angle
14.1.5.4
Settings
Table 362:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
3I0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
3I0Min
0 - 500000
A
1
0
Minimum value
3I0Max
0 - 500000
A
1
3300
Maximum value
3I0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
3I0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I1Min
0 - 500000
A
1
0
Minimum value
I1Max
0 - 500000
A
1
1300
Maximum value
I1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
I2Min
0 - 500000
A
1
0
Minimum value
I2Max
0 - 500000
A
1
1300
Maximum value
I2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is common
for all limits
I2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Section 14
1MRK 502 048-UUS A
Monitoring
520
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...