Name
Values (Range)
Unit
Step
Default
Description
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
VTsec5
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim5
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec6
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim6
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 6:
AIM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
Table continues on next page
1MRK 502 048-UUS A
Section 3
Analog inputs
53
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...