a
b
a>b
OR
|I
OP
|
STx
AND
Pickupx
Characteristx=DefTime
DirModeSelx=Disa bled
DirModeSelx=Non-dire ctional
DirModeSelx=Forward
DirModeSelx=Reverse
AND
AND
FORWARD_Int
REVERSE_Int
OR
OR
STAGE x_DIR_Int
ANSI12000008-3-en.vsd
AND
AND
Characteristx=Inve rse
Inve rse
ANSI12000008-3-en.vsd
0
0-tx
0
0-txMin
PUx
ANSI12000008 V3 EN
Figure 90:
Simplified logic diagram for OC4PTOC
8.1.8
Second harmonic blocking element
A harmonic restrain of the Four step overcurrent protection function OC4PTOC 51_67
can be chosen. If the ratio of the 2nd harmonic component in relation to the fundamental
frequency component in the residual current exceeds the preset level defined by parameter
2ndHarmStab
setting, any of the four overcurrent stages can be selectively blocked by
parameter
HarmRestrainx
setting. When 2nd harmonic restraint feature is active, the
OC4PTOC 51_67 function output signal 2NDHARMD will be set to logical value one.
a
b
a>b
BLOCK
AND
I
OP
Extract second
harmonic current
component
Extract
fundamental
current component
X
2ndHarmStab
a
b
a>b
a
b
a>b
0.07*IBase
IEC13000014-1-en.vsd
2NDHARMD
2ndH_BLOCK_Int
IEC13000014 V1 EN
Figure 91:
Second harmonic blocking
Section 8
1MRK 502 048-UUS A
Current protection
202
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...