Time in milliseconds
→
pos. seq. current in kA
trip command to CB
rotor angle in radian
fault
occurs
←
normal load current
←
min. current
very high currents due
to out-of-step condition
←
after 1st
pole slip
←
2nd
←
rotor angle
angle towards 0°
current decreases
fault cleared
→
current increases under
fault conditions
→
←
tBreaker = 60 ms
trip command
→
issued here
IEC10000115-1-en.vsd
IEC10000115 V1 EN
Figure 82:
Trip initiation when the break-time of the circuit breaker is known
7.4.7.5
Design
When the complex impedance Z(R, X) enters the limit-of-reach region, the algorithm
determines the direction impedance Z moves, that is, the direction the lens is traversed and
measures the time taken to traverse the lens from one side to the other. If the traverse time
is more than the limit 40 or 50 ms, a pole-slip is declared. If the complex impedance Z(R,
X) exits the lens on the same side it entered, then it is a stable case and the protected
machine is still in synchronism. If a pole-slip has been detected, then it is determined in
which zone the centre of oscillation is located. If the number of actual pole-slips exceeds
the maximum number of allowed pole-slips in either of the zones, a trip command is
issued taking care of the circuit breaker safety.
Section 7
1MRK 502 048-UUS A
Impedance protection
186
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...