![ABB 650 series Technical Manual Download Page 518](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503518.webp)
Name
Values (Range)
Unit
Step
Default
Description
PDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
PZeroDb
0 - 100000
m%
1
500
Zero point clamping
PHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
PLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
PLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
PLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
QDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
QZeroDb
0 - 100000
m%
1
500
Zero point clamping
QHiHiLim
-2000.0 - 2000.0
%SB
0.1
150.0
High High limit in % of SBase
QHiLim
-2000.0 - 2000.0
%SB
0.1
120.0
High limit in % of SBase
QLowLim
-2000.0 - 2000.0
%SB
0.1
-120.0
Low limit in % of SBase
QLowLowLim
-2000.0 - 2000.0
%SB
0.1
-150.0
Low Low limit in % of SBase
QLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
UGenZeroDb
1 - 100
%VB
1
5
Zero point clamping in % of VBase
PFDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
PFZeroDb
0 - 100000
m%
1
500
Zero point clamping
IGenZeroDb
1 - 100
%IB
1
5
Zero point clamping in % of IBase
PFHiHiLim
-1.000 - 1.000
-
0.001
1.000
High High limit (physical value)
PFHiLim
-1.000 - 1.000
-
0.001
0.800
High limit (physical value)
PFLowLim
-1.000 - 1.000
-
0.001
-0.800
Low limit (physical value)
PFLowLowLim
-1.000 - 1.000
-
0.001
-1.000
Low Low limit (physical value)
PFLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
UDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
UZeroDb
0 - 100000
m%
1
500
Zero point clamping
UHiHiLim
0.0 - 200.0
%VB
0.1
150.0
High High limit in % of UBase
UHiLim
0.0 - 200.0
%VB
0.1
120.0
High limit in % of VBase
ULowLim
0.0 - 200.0
%VB
0.1
80.0
Low limit in % of VBase
ULowLowLim
0.0 - 200.0
%VB
0.1
60.0
Low Low limit in % of VBase
ULimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common for all
limits)
IDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
IZeroDb
0 - 100000
m%
1
500
Zero point clamping
Table continues on next page
Section 14
1MRK 502 048-UUS A
Monitoring
512
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...