17.16.2.5
Monitored data
Table 527:
DOSFRNT Monitored data
Name
Type
Values (Range)
Unit
Description
State
INTEGER
0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
Frame rate control state
Quota
INTEGER
-
%
Quota level in percent 0-100
IPPackRecNorm
INTEGER
-
-
Number of IP packets
received in normal mode
IPPackRecPoll
INTEGER
-
-
Number of IP packets
received in polled mode
IPPackDisc
INTEGER
-
-
Number of IP packets
discarded
NonIPPackRecNorm
INTEGER
-
-
Number of non IP packets
received in normal mode
NonIPPackRecPoll
INTEGER
-
-
Number of non IP packets
received in polled mode
NonIPPackDisc
INTEGER
-
-
Number of non IP packets
discarded
17.16.3
Denial of service, frame rate control for LAN1 port DOSLAN1
17.16.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Denial of service, frame rate control for
LAN1 port
DOSLAN1
-
-
17.16.3.2
Function block
DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
IEC09000134 V1 EN
Figure 313:
DOSLAN1 function block
1MRK 502 048-UUS A
Section 17
Basic IED functions
705
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...