14.24.1
Functionality
I103SUPERV is a function block with defined functions for supervision indications in
monitor direction. This block includes the
FunctionType
parameter, and the information
number parameter is defined for each output signal.
14.24.2
Function block
IEC10000293-1-en.vsd
I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN
Figure 282:
I103SUPERV function block
14.24.3
Signals
Table 445:
I103SUPERV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
32_MEASI
BOOLEAN
0
Information number 32, measurand supervision of I
33_MEASU
BOOLEAN
0
Information number 33, measurand supervision of U
37_IBKUP
BOOLEAN
0
Information number 37, I high-high back-up protection
38_VTFF
BOOLEAN
0
Information number 38, fuse failure VT
46_GRWA
BOOLEAN
0
Information number 46, group warning
47_GRAL
BOOLEAN
0
Information number 47, group alarm
14.24.4
Settings
Table 446:
I103SUPERV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
Section 14
1MRK 502 048-UUS A
Monitoring
626
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...