Name
Values (Range)
Unit
Step
Default
Description
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves for
step 1
TD1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay for
step 1
OperationStep2
Disabled
Enabled
-
-
Enabled
Enable execution of step 2
OpMode2
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1 of 3, 2
of 3, 3 of 3) from step 2
Pickup2
1 - 100
%VB
1
50
Voltage start value (DT & IDMT) in % of VBase
for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definie time delay of step 2
Table 157:
UV2PTUV (27) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
-
-
PhN DFT
Group selector for connection type
9.1.6
Monitored data
Table 158:
UV2PTUV (27) Monitored data
Name
Type
Values (Range)
Unit
Description
V_A
REAL
-
kV
Voltage in phase A
V_B
REAL
-
kV
Voltage in phase B
V_C
REAL
-
kV
Voltage in phase C
9.1.7
Operation principle
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system
voltage. UV2PTUV (27) has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding PICKUP
signal is generated. UV2PTUV (27) can be set to PICKUP/TRIP based on
1 out of 3
,
2 out
of 3
or
3 out of 3
of the measured voltages, being below the set point. If the voltage remains
below the set value for a time period corresponding to the chosen time delay, the
corresponding trip signal is issued. The time delay characteristic is settable for step 1 and
can be either definite or inverse time delayed. Step 2 is always definite time delayed.
1MRK 502 048-UUS A
Section 9
Voltage protection
283
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...