8.2.5
Settings
Table 92:
EF4PTOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
EnaDir
Disable
Enable
-
-
Enable
Enabling the Directional calculation
AngleRCA
-180 - 180
Deg
1
65
Relay characteristic angle (RCA)
polMethod
Voltage
Current
Dual
-
-
Voltage
Type of polarization
UPolMin
1 - 100
%UB
1
1
Minimum voltage level for polarization (UN or
U2) in % of UBase
IPolMin
2 - 100
%IB
1
5
Minimum current level for polarization (IN or I2)
in % of IBase
RPol
0.50 - 1000.00
ohm
0.01
5.00
Real part of source Z to be used for current
polarisation
XPol
0.50 - 3000.00
ohm
0.01
40.00
Imaginary part of source Z to be used for
current polarisation
I>Dir
1 - 100
%IB
1
10
Current level (IN or I2) for direction release in %
of IBase
2ndHarmStab
5 - 100
%
1
20
Second harmonic restrain operation in % of IN
amplitude
DirMode1
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (off, non-directional,
forward, reverse)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
-
-
ANSI Def. Time
Time delay curve type for step 1
IN1>
1 - 2500
%IB
1
100
Operate residual current level for step 1 in % of
IBase
t1
0.000 - 60.000
s
0.001
0.000
Independent (definite) time delay of step 1
Table continues on next page
Section 8
1MRK 502 048-UUS A
Current protection
206
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...