LEDs set for sequence 6 are completely independent in its operation of LEDs set for other
sequences.
Timing diagram for sequence 6
shows the timing diagram for two indications within one disturbance.
IEC01000239_2-en.vsd
Activating
signal 2
LED 2
Manual
reset
Activating
signal 1
Automatic
reset
LED 1
Disturbance
tRestart
IEC01000239 V2 EN
Figure 22:
Operating sequence 6 (LatchedReset-S), two indications within same
disturbance
shows the timing diagram for a new indication after
tRestart
time has elapsed.
1MRK 502 048-UUS A
Section 5
Local Human-Machine-Interface LHMI
79
Technical manual