Function
Range or value
Accuracy
Reactive power, Q
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
± 1.0% of S
n
at S ≤ S
n
± 1.0% of S at S > S
n
Apparent power, S
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
± 1.0% of S
n
at S ≤ S
n
± 1.0% of S at S > S
n
Apparent power, S Three phase
settings
cos phi = 1
± 0.5% of S at S > S
n
± 0.5% of S
n
at S ≤ S
n
Power factor, cos (φ)
0.1 x V
n
< V < 1.5 x V
n
0.2 x I
n
< I < 4.0 x I
n
< 0.02
14.2
Event Counter CNTGGIO
14.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event counter
CNTGGIO
S00946 V1 EN
-
14.2.2
Functionality
Event counter CNTGGIO has six counters which are used for storing the number of times
each counter input has been activated.
14.2.3
Function block
CNTGGIO
BLOCK
COUNTER1
COUNTER2
COUNTER3
COUNTER4
COUNTER5
COUNTER6
RESET
VALUE1
VALUE2
VALUE3
VALUE4
VALUE5
VALUE6
IEC09000090_1_en.vsd
IEC09000090 V1 EN
Figure 247:
CNTGGIO function block
Section 14
1MRK 502 048-UUS A
Monitoring
538
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...