![ABB 650 series Technical Manual Download Page 92](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503092.webp)
load tap changer as well as for shunt reactors including local feeders within the station. An
adaptive stabilizing feature is included to avoid misoperations during for heavy through-
faults.
Harmonic restraint is included for inrush and overexcitation currents respectively, cross-
blocking is also available. Adaptive harmonic restraint is also included for system
recovery inrush and CT saturation during external faults. A high set unrestrained
differential current protection element is included for a very high speed tripping at a high
internal fault currents.
Included is an innovative sensitive differential protection element based on the theory of
symmetrical components. This element offers the best possible coverage of power
transformer windings turn to turn faults.
6.1.2
Transformer differential protection, three winding T3WPDIF
(87T)
6.1.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transformer differential protection,
three-winding
T3WPDIF
3Id/I
SYMBOL-BB V1 EN
87T
Section 6
1MRK 502 048-UUS A
Differential protection
86
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...