BLOCK
CountType
INPUT
RESET
ERROR
OVERFLOW
LIMIT1 … 4
CounterLimit1...4
MaxValue
OnMaxValue
InitialValue
VALUE
Operation
Counter
Overflow
Detection
Limit
Check
Error
Detection
IEC12000625_1_en.vsd
IEC12000625 V1 EN
Figure 248:
Logic diagram
The counter can be initialized to count from a settable non-zero value after reset of the
function. The function has also a maximum counted value check. The three possibilities
after reaching the maximum counted value are:
•
Stops counting and activates a steady overflow indication for the next count
•
Rolls over to zero and activates a steady overflow indication for the next count
•
Rolls over to zero and activates a pulsed overflow indication for the next count
The pulsed overflow output lasts up to the first count after rolling over to zero, as
illustrated in figure
.
IEC12000626_1_en.vsd
Max value +3
®
Max value -1
®
Max value
®
Max value +1
®
Max value +2
®
Max value -1
®
Max value
®
0
®
1
2
...
...
...
...
Overflow indication
Actual value
Counted value
IEC12000626 V1 EN
Figure 249:
Overflow indication when OnMaxValue is set to rollover pulsed
Section 14
1MRK 502 048-UUS A
Monitoring
542
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...