![ABB 650 series Technical Manual Download Page 254](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503254.webp)
8.6.3
Function block
ANSI08000041-1-en.vsd
CCRPLD (52PD)
I3P*
BLOCK
CLOSECMD
OPENCMD
EXTPDIND
TRIP
PICKUP
ANSI08000041 V1 EN
Figure 113:
CCRPLD (52PD) function block
8.6.4
Signals
Table 115:
CCRPLD (52PD) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
CLOSECMD
BOOLEAN
0
Close command to CB
OPENCMD
BOOLEAN
0
Open command to CB
EXTPDIND
BOOLEAN
0
Pole discrepancy signal from CB logic
Table 116:
CCRPLD (52PD) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal to CB
PICKUP
BOOLEAN
Trip condition TRUE, waiting for time delay
8.6.5
Settings
Table 117:
CCRPLD (52PD) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
tTrip
0.000 - 60.000
s
0.001
0.300
Time delay between trip condition and trip
signal
ContactSel
Disabled
PD signal from CB
-
-
Disabled
Contact function selection
Table continues on next page
Section 8
1MRK 502 048-UUS A
Current protection
248
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...