![ABB 650 series Technical Manual Download Page 748](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503748.webp)
Table 578:
Inverse time characteristics for undervoltage protection
Function
Range or value
Accuracy
Type A curve:
=
-
æ
ö
ç
÷
è
ø
td
t
VPickup V
VPickup
EQUATION1658 V1 EN
V = V
measured
td = (0.05-1.10) in steps of
0.01
±5% +60 ms
Type B curve:
×
=
+
-
×
-
æ
ö
ç
÷
è
ø
2.0
480
0.055
32
0.5
td
t
VPickup V
VPickup
EQUATION1659 V1 EN
V = V
measured
td = (0.05-1.10) in steps of
0.01
Table 579:
Inverse time characteristics for residual overvoltage protection
Function
Range or value
Accuracy
Type A curve:
=
-
æ
ö
ç
÷
è
ø
t
td
V
VPickup
VPickup
EQUATION1661 V1 EN
V = V
measured
td = (0.05-1.10) in steps of
0.01
±5% +70 ms
Type B curve:
=
×
-
×
-
-
æ
ö
ç
÷
è
ø
2.0
480
32
0.5
0.035
t
td
V
VPickup
VPickup
EQUATION1662 V1 EN
td = (0.05-1.10) in steps of
0.01
Type C curve:
=
×
-
×
-
-
æ
ö
ç
÷
è
ø
3.0
480
32
0.5
0.035
t
td
V
VPickup
VPickup
EQUATION1663 V1 EN
td = (0.05-1.10) in steps of
0.01
Section 21
1MRK 502 048-UUS A
Time inverse characteristics
742
Technical manual
Summary of Contents for 650 series
Page 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Page 2: ......
Page 44: ...38 ...
Page 62: ...56 ...
Page 68: ...62 ...
Page 156: ...150 ...
Page 198: ...192 ...
Page 512: ...506 ...
Page 644: ...638 ...
Page 714: ...708 ...
Page 777: ...771 ...