ZENN
iO
AVANCE Y TECNOLOGÍA
vwww.zennio.com
47
SECTION
NUMBER
SIZE
IN/OUT
FLAGS
VALUES
NAME
DESCRIPTION
RANGE
1
st
TIME
RESET
THERMOSTAT
194-195
1 bit
I
W
0/1
0
Indifferent
[Tx] Offset Reset
Reset offset
196-197
1 bit
I
W
0/1
As Param
Last
[Tx] Mode
0=Cool; 1=Heat
198-199
1 bit
O
RT
0/1
As Param
Last
[Tx] Mode (Status)
0=Cool; 1=Heat
200-201
1 bit
I
W
0/1
As Param
As Param
[Tx] ON/OFF
0=Off; 1=On
202-203
1 bit
O
RT
0/1
As Param
As Param
[Tx] ON/OFF (Status)
0=Off; 1=On
204, 206
1 bit
O
RT
0/1
0
Last
[Tx] Control variable (Cool)
PI control (PWM)
[Tx] Control variable (Cool)
2-point control
205, 207
1 bit
O
RT
0/1
0
Last
[Tx] Control variable (Heat)
PI control (PWM)
[Tx] Control variable (Heat)
2-point control
208, 210
1 byte
O
RT
0-100%
0
Last
[Tx] Control variable (Cool)
PI control (Continuous)
209, 211
1 byte
O
RT
0-100%
0
Last
[Tx] Control variable (Heat)
PI control (Continuous)
212, 214
1 bit
O
RT
0/1
0
Last
[Tx] Additional Cool
Temp > (SBand) => "1"
213, 215
1 bit
O
RT
0/1
0
Last
[Tx] Additional Heat
Temp < (Setpoint-Band) => "1"