ZENN
iO
AVANCE Y TECNOLOGÍA
vwww.zennio.com
21
21
communication object "[Internal Sensor] Current Temperature". The value 0 indicates that
the periodical sending is disabled.
Send with a temperature change:
ZAS can also send to the KNX bus the current
temperature value when it detects, compared to the previous reading, a change (increase
or decrease) of at least the amount of degrees specified in this parameter (from 0 to 200
tenths of a degree). To disable this sending, just set a 0 for this field.
Temperature protection:
permits enabling overheating, overcooling or both
protections. Depending on the selected protection, one or two communication objects will
be enabled: "[Internal Sensor] Overheating" and "[Internal Sensor] Overcooling", which
will indicate (with the value "1") if the corresponding limit has been exceeded. It is
necessary to define the overheating or the overcooling temperature (or both), in degrees,
as well as a hysteresis value (tenths of a degree).
Contrast level:
the initial contrast level of the display can be set (0-20). This value can be
changed later, if the contrast function of the configuration page is activated.
Buzzer object.
Associated to this parameter is the 1-bit communication object "[General]
Buzzer", which will make ZAS emit a beep when receiving the value "1". The value "0" does
not cause any action.
Note:
Take into account that for this beep to be emitted, the buzzer must be enabled
("[General] Buzzer enabling"=1).
3.3. PAGES
From this section it is possible to enable and configure individually the pages to be
implemented in ZAS.