Access by pressing the last button on the right of the inverter under Discharge depth:
4.
Depth of discharge
5.
Tax on forced labour
6.
Save
Set the discharge depth and discharge depth in EPS.
For example, if the discharge depth = 50% and the discharge depth EPS = 80%, while the network is
connected: the inverter does not discharge the battery when the SOC is less than 50%.
In case of power failure: the inverter will operate in EPS mode (if EPS mode is enabled) and will continue to
drain the battery until the battery SOC is not less than 20%.
Discharge depth
50%
Depth of discharge EPS
80%
EPS Safety Safety Buffer
20%